DRI-U_SERIES

DRI-U_SERIES

分  类:测量测试仪器

品  牌:欧米茄

厂  商:Omega工业测量(中国)

型  号:DRI-U_SERIES

相关行业:

发布时间:2019-12-19 16:48 浏览人数:

最新产品

产品详情
参数
包装

DIN Rail Signal Conditioner with Universal Input

The DRI-U Series is a DIN rail mount,thermocouple, RTD, resistance or voltageinput signal conditioner with 1800V isolationbetween input, output and power. The fieldconfigurable input and output offers flexible,wide ranging capability for most temperaturesignal conditioning applications. The DRI-U Seriesis configured via DIP switch for Types J, K, T, E, R,S, B, N, or C thermocouples or Pt, Ni or Cu RTDs.Additionally, functions such as signal linearization, up ordown-scale burnout, number of RTD leads (2, 3 or 4) andvoltage or current output are also set via dip-switches.

Cold-junction compensation for accuracy and performance

Accuracy and performance during warm-up and duringchanges in ambient temperature are maximized.The cold-junction compensation technique utilizestwo temperature sensors to measure the differentialtemperature near the terminal block. Using heat transfercalculations with the measured differential temperatureand the known thermal conductivity of the PCB, theterminal junction temperature is determined with extremeaccuracy. Even during unstable thermal states such asstart-up, ambient temperature changes or changing loador power, the DRI-U Series performs extremely accuratethermocouple temperature measurement.

Quick and accurate calibration checks

System performance and productivity are improveddue to reduced warm up time, fewer temperaturemeasurement errors and tighter process control forhigher quality. Most significantly, it allows calibration tobe checked quickly and accurately without the effectsof rapid ambient temperature changes due to openinga control panel door, which often causes erroneousreadings and miscalibrations that are a common causeof measurement errors.

Easy field ranging for any thermocouple or RTD input types

Touch calibration technology allows easy field rangingfor any of the thermocouple or RTD input types. Forexample, the dip-switch configured range for the J Typethermocouple is -210 to 760°C (-346 to 1400°F). Using athermocouple simulator as a reference, the DRI-U Seriescould be ranged for 0 to 50°C (32 to 122°F) or0 to 500°C (32 to 932°F) by simply applying the desiredminimum and maximum input levels and pushing therange button to store the levels in non-volatile memory.The output is ranged by applying an input signal toachieve an accurate output level and pushing the rangebutton.

The DRI-U Series field configurable thermocouple orRTD input signal conditioner is useful in eliminatingground loops and interfacing temperature sensorsto data acquisition and control systems. Three-wayisolation completely eliminates ground loops from anysource. Isolation protects expensive SCADA systemsfrom ground faults and allows the noise reductionbenefits of grounded thermocouples or sensors to berealized.

The DRI-U Series employs the latest analog to digitalsignal processing technology and advanced low-powermicroprocessors. Cold junction compensation (CJC)of thermocouples, and lead length compensation forRTDs ensures an extremely accurate and stable signalfor virtually any temperature sensor to DC signalconversion.

High density DIN rail mounting offers a very compactsolution and saves valuable panel space. Power isdelivered to the DRI-U Series using the exclusiveACPB (AC power) or DCPB (DC power) rail whichreduces wiring requirements and the need to daisychainpower. Plug-in screw terminals ensure easyinstallation and low Mean-Time-To-Repair (MTTR).

The DRI-U Series is equipped with front panel LEDsfor input power (green-on), input overrange andunderrange; input open circuit (yellow-on); and switchsetting error (red-on).

The DRI-U Series can be configured via dip-switchesfor a wide variety of temperature input ranges for RTD,thermocouple, resistance and voltage inputs. Inputscan be offset by >90% or adjusted down to <10% ofthe full scale span.

The factory default configuration for the DRI-U Series is as follows:

Input Type: Thermocouple, Type J
Input Range: 0 to 500°C (32 to 932°F)
Burnout: Upscale
Output Range: 4 to 20 mA

Specifications
INPUT
Input Types and Ranges:
See tables
Impedance: ≥1.0 MΩ typical for thermocouple and voltage inputs
RTD Excitation: ≤ 0.3 mA
Burnout Detection: Upscale or downscale
CJC Error: ≤±0.1°C max (the output is ensured to be within ±0.5°C of rated accuracy 30 seconds after powering)

OUTPUT
Voltage:

    Range: DRI-U-AC; 0 to 10V: DRI-U-DC; 0 to 5V or 2 to 10V
    Drive: 10 mA (1000 Ω load min)
Current:
    Range: DRI-U-AC: 0 to 20 mA; DRI-U-DC; 0 to 20 mA,4 to 20 mA
    Drive: 15V (750 Ω max)
Isolation: 1800 Vdc or peak AC between input, output and power
Configuration:
    Range: SW1:
Pushbutton, input and output ranging
    Range: SW2: Linearization, burnout, output (voltage or current), and initialization mode
    Range: SW3:
Input type
Accuracy:
    Input A/D: See tables
    Linearization: ≤±0.05% of accuracy range max
    Output: ≤±10 mA for current output; ≤±5 mV for voltage output
Thermal Stability:
    CJC: ±0.01°C/°C change in ambient max
    Zero: ±0.0075% of full scale/°C change in ambient max
    Span: ±0.0075% of full scale/°C change in ambient max
    Long Term: ±0.1% max over a 9 month period
Response Time: 400 msec, typical
Turn On Time: ≤5 seconds to establish output within 99% or 2°C of final value or 0.5°C within 30 seconds
LED Indicator:
    Power (Green): On when power is on, flashes for thermocouple burnout
    Input (Yellow): Flashes for out of range
    Red: Flashes for switch setting error
    Calibration: 1 green, 1 yellow and 1 red LEDs indicatesteps in ranging process
Common Mode Rejection: 120 dB at DC, > 90 dB at 60 Hz
ESD Susceptibility: Capable of meeting IEC 801-2 level 3 (8 kV)
Humidity (Non-Condensing):
    Operating: 15 to 95% RH @ 45°C (113°F)
    Soak: 90% RH for 24 Hours @ 60°C (140°F)
Temperature:
    Operating: -25 to 65°C (-13 to 149°F)
    Storage: -25 to 70°C (-13 to 158°F)
Power:
    DRI-U-AC: 100 to 240 Vac ± 10%, 50 to 400 Hz; 2.5 W max
    DRI-U-DC: 9 to 30 Vdc ± 10%; 2.5 W max
Wire Terminal: Socketed screw terminals for 12 to 22 AWG
Weight: 227 g (0.50 lb)









































































暂无内容提供
暂无内容提供

联系方式

中国自动化网安全提示,在购买供应商商品时,请一定要先审核好企业信息是否真实,谨防网上诈骗。
公司名称:Omega工业测量(中国)
联系人: 王先生
联系电话:02161973664
手机号:
传 真:
电子信箱:kevin.wang@cn.omega.com
公司网站:http://cn.omega.com
公司地址:上海市宜山路1698号102单元
留言反馈
  • 评价:

  • 关于:

  • 联系人:

  • 联系电话:

  • 联系邮箱:

  • 需求意向:

  • 验证码:

    看不清楚?

  • 在线咨询
X
下载企业APP

成为企业会员免费生成APP!