DRSL-TC_Series

DRSL-TC_Series

分  类:压力传感器

品  牌:欧米茄

厂  商:Omega工业测量(中国)

型  号:DRSL-TC_Series

相关行业:

发布时间:2019-12-19 16:40 浏览人数:

最新产品

产品详情
参数
包装
  • DRSL-TC Non-Isolated and DRSL-TC-ISO Isolated Models
  • Accepts Type J and Type K Thermocouples
  • Pre-Calibrated Temperature Ranges Selectable via Dip-Switches
  • Slimline Housing—Only 6 mm (0.24") Wide
  • High Accuracy
  • Fast Response Time <30 ms/300 ms (Selectable)
  • Excellent EMC Performance and 50/60 Hz Noise Suppression

  • The DRSL-TC Series thermocoupleinput DIN rail signal conditionersprovide a competitive choice in termsof both price and technology forinterfacing thermocouple inputs toSCADA systems or PLC equipment.

    The DRSL-TC and DRSL-TC-ISOcan be used for signal conversion ofstandard Type J or K thermocoupleinputs into unipolar analog signals.

    The DRSL-TC-ISO isolated modeloffers 3-way isolation between input,output and supply and provides surgesuppression and protects controlsystems from transients and noise.Low power consumption facilitatesDIN rail mounting without the needfor any air gap. Easy configurationof more than 1000 factory calibratedmeasurement ranges is done viaDIP-switches. The unit operates overa wide temperature range from-25 to 70°C (-13 to 158°F).

    SPECIFICATIONS
    INPUT
    Type: J or K thermocouple
    Temperature Range
        Type J: -100 to 1200°C (-148 to 2192°F)
        Type K: -180 to 1372°C (-292 to 2501°F)
    Sensor and Cable Specifications: 5 kΩ per wire
    Cold Junction Compensation (CJC): Internal or external (selectable)
    CJC Accuracy via External CJC (Pt100 RTD Sensor): Better than ±0.15°C (DRSL-TC-ISO only)
    CJC via Internally Mounted Sensor: Better than ±2.5°C
    Open Thermocouple Detection: Yes (DIP switch selectable upscale or downscale)

    OUTPUT
    Current Output
    Programmable Signal Ranges: 0 to 20 and 4 to 20 mA
    Range Limits (NAMUR NE43 Out of Range): Below 3.8 mA or above 20.5 mA for 4 to 20 mA output; 0 mA or above 20.5 mA for 0 to 20 mA output
    Sensor Error Detection (Dip Switch Selectable for Enable or None): Below 3.5 mA or above 23 mA for 4 to 20 mA output; 0 mA or above 23 mA for 0 to 20 mA output
    Incorrect DIP-Switch Setting Identification: 0 mA
    Output Error Level: DIP switch selectable for upscale or downscale
    Load: 21 mA/600 Ω /12.6V max
    Load Stability: ≤0.01% of span/100 Ω
    Voltage Output
    Programmable Signal Ranges: 0 to 10V, 2 to 10V, 0 to 5V and 1 to 5V
    Range Limits (Out of Range): Range ±2.5%
    Incorrect DIP Switch Setting Identification: 0V
    Load: >10 kΩ min

    GENERAL
    Supply Voltage:
    DRSL-TC: 16.8 to 31.2 Vdc via connectors
    DRSL-TC-ISO: 16.8 to 31.2 Vdc via power rail or connectors
    Power Consumption: 0.7 W max
    Internal Consumption: 0.65 W max
    Isolation (DRSL-TC-ISO Only): Input/output/supply
    Isolation Voltage, Test (DRSL-TC-ISO Only): 2.5 kVac (reinforced)
    Isolation Voltage, Working (DRSL-TC-ISO Only): 300 Vac
    Status LED: Green LED indicates operational status of the unit and input sensor
        Normal Operation: Flashes for 15 ms at 13 Hz rate
        Sensor Error: Flashes for 15 ms at 1 Hz rate
        Incorrect DIP Switch Setting: Flashes for 500 ms at 1 Hz rate
        Hardware Failure: LED off
    Signal/Noise Ratio: >60 dB
    Response Time (0 to 90%, 100 to 10%): <30 ms/300 ms (selectable, provides either fast response or signal dampening as needed)
    Accuracy:
        DRSL-TC: Better than 1.0°C or ±0.1% of selected input range
        DRSL-TC-ISO: Better than 0.5°C or ±0.05% of selected input range
    Temperature Coefficient: ≤±0.1°C/°C or ≤±0.01%/°C
    EMC Immunity Influence: <±0.5% of span
    Extended EMC Immunity NAMUR NE 21, A Criterion, Burst: <±1% of span (span = selected input range)

    ENVIRONMENTAL
    Operating Temperature: -25 to 70°C (-13 to 158°F)
    Storage Temperature: -40 to 85°C (-40 to 185°F)
    Calibration Temperature: 20 to 28°C (68 to 82°F)
    Relative Humidity: 0 to 95% RH non-condensing
    Protection Degree: IP20
    Installation Area: Pollution degree 2 and measurement/overvoltage category II

    MECHANICAL
    Dimensions: 113 H x 6.1 W x 115 mm D (4.4 x 0.24 x 4.5")
    Weight: 70 g (0.15 lb) approx
    DIN Rail Type: DIN EN 60715 - 35 mm
    Wire Size: 0.13 x 2.5 mm²/ AWG 26 to 12 stranded wire
    Screw Terminal Torque: 0.5 Nm



暂无内容提供
暂无内容提供

联系方式

中国自动化网安全提示,在购买供应商商品时,请一定要先审核好企业信息是否真实,谨防网上诈骗。
公司名称:Omega工业测量(中国)
联系人: 王先生
联系电话:02161973664
手机号:
传 真:
电子信箱:kevin.wang@cn.omega.com
公司网站:http://cn.omega.com
公司地址:上海市宜山路1698号102单元
留言反馈